DKG-705 AMF, PARALLEL TO MAINS AND DUAL GENSET SYNCHRONIZATION UNIT WITH J1939 INTERFACE
The DKG-705 is a comprehensive AMF unit for single or dual generating set operating in standby or parallel with mains modes.
The DKG-705 unit is able to transfer the load between mains and genset in 4 different ways:
-transfer with interruption
-no break transfer without synchronization
-no break transfer with synchronization
-soft transfer
Read More...In AUTOMATIC position, DKG-705 monitors mains phase voltages and controls the automatic starting, stopping and load transfer of the generating set in case of a mains failure and once the generator is running, it monitors internal protections and external fault inputs.
If a fault condition occurs, the unit shuts down the engine automatically, indicates the failure source on the LCD display and turns on the red ALARM led.
The unit connects to ECU controlled electronic engines through its standard J1939 CANBUS port, providing engine control, protection and instrumentation without extra senders.
Various engine parameters are available in display pages. The ECU alarms are displayed in text together with SPN-FMI codes.
Automatic mains failure J1939 engine monitoring and control port Various engine brands and models available Engine control Generator protection Built in alarms and warnings True RMS measurements Complete genset power measurements Complete mains power measurements Synchroscope Governor and AVR control interfaces No break transfer & no break load test Soft transfer with ramp control Single genset power export to mains Single genset peak lopping (peak shaving) Dual genset synchronization & load sharing Dual genset soft transfer to / from mains KW/KVAr load control G-59 mains protections Battery backed-up real time clock Daily, weekly, monthly exerciser Remote start operation capability Gas engine support Mains simulation input Engine Idle speed control Load shedding |
Periodic maintenance request indicator Event logging with time stamp Statistical counters Weekly operation schedule programs Field adjustable parameters RS-232 serial port Upgrade software downloadable from serial port Free MS-Windows Remote monitoring SW: -local, LAN, IP and modem connection -monitoring, download of parameters -download of software updates -modem networking GSM SMS message sending on fault GSM and PSTN modem calls on fault MODBUS communications LCD display 4 lines by 20 characters Dual language support Output expansion capability Configurable analogue inputs: 4 Configurable digital inputs: 8 Configurable relay outputs: 7 Survives cranking dropouts Sealed front panel (IP65) Plug-in connection system for easy replacement |